Your Search for Proximity Sensors Starts with the World-leading Performance and Quality of the E2E. Standard Sensors for detecting ferrous metals. Wide array of variations. Ideal for a variety of applications. Models with different frequencies are also available to prevent mutual interference. Superior environment resistance with standard cable made of oil resistant PVC and sensing surface made of material that resists cutting oil. Cable protector provided as a standard feature.
omron-E2E-X14MD1-2M
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2014632
Manufacturer Part Number:
E2E-X14MD1 2M
EAN:
4547648406253
Brand/Manufacturer
OMRON
Unit of Measure:
PCS

Specification

Cascadable:
yes
Coating housing:
Nickel-plated
Compression-resistant:
no
Construction type housing:
Cylinder, screw-thread
Degree of protection (NEMA):
Other
Diameter sensor:
18 mm
Explosion safety category for dust:
None
Explosion safety category for gas:
None
Height of sensor:
24 mm
Housing material:
Metal
Length of sensor:
38 mm
Max. output current at protected output:
100 mA
Mechanical mounting condition for sensor:
Not flat
Number of contact energized outputs with signalling function:
0
Number of protected contact energized outputs:
0
Number of protected semiconductor outputs:
0
Number of semiconductor outputs with signalling function:
1
Performance level according to EN ISO 13849-1:
None
Rated control supply voltage AC 50 Hz:
0...0 V
Rated control supply voltage AC 60 Hz:
0...0 V
Rated control supply voltage DC:
12...24 V
SIL according to IEC 61508:
None
Suitable for safety functions:
no
Supply voltage:
10...30 V
Switching distance:
14 mm
Switching frequency:
400 Hz
Type of actuation:
Metallic Target
Type of electric connection:
Cable
Type of interface:
None
Type of interface for safety communication:
None
Type of switch function:
Normally open contact
Type of switching output:
2-wire
Voltage type:
DC
Width sensor:
24 mm
With monitoring function downstream switching devices:
no