• (0)
ABB

S804S-C63 MCB 63A 4P 50KA C CURVE

2CCS864001R0634
2031026

Sign in to view price

The S804S-C63 is a 4-pole High Performance Circuit breaker with C-characteristic, with cage terminal and a rated current of 63 A. It is a current limiting device with a maximum breaking capacity of 50kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S804S-C63 complies with IEC/EN 60898-1 and IEC/EN 60947-2 and allows the use for residential, commercial and industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S804S-C63 more comfortable. Due to the fast arc extinction of S804S-C63 your application will be secured.
abb-2CCS864001R0634
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2031026
Manufacturer Part Number:
2CCS864001R0634
EAN:
7612271200923
Brand/Manufacturer
ABB
Unit of Measure:
PCS

Specification

Additional equipment possible:
yes
Ambient temperature during operating:
-25...60 °C
Built-in depth:
82.5 mm
Concurrently switching neutral conductor:
no
Connectable conductor cross section multi-wired:
0...70 mm²
Connectable conductor cross section solid-core:
0...50 mm²
Current limiting class:
3
Degree of protection (IP):
IP20
Flush-mounted installation:
no
Frequency:
50...60 Hz
Number of poles (total):
4
Number of protected poles:
4
Over voltage category:
3
Pollution degree:
3
Rated current:
63 A
Rated impulse withstand voltage Uimp:
8 kV
Rated insulation voltage Ui:
690 V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V:
25 kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V:
25 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V:
50 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V:
50 kA
Rated voltage:
690 V
Release characteristic:
C
Voltage type:
AC
Width in number of modular spacings:
4