• (0)

DN3-400N MCCB 400A 3P 50KA

CM94003OOR1OG
2039743

Sign in to view price

- Conforms to IS/IEC 60947-2 & IEC 60947-2 - Range: 40A to 1250A, 3P & 4P - Choice of 36kA / 50kA / 70kA breaking capacities - Ics = 100% Icu - Suitable for Isolation - Adjustable Over Load from 0.4 - 1.0 x In - Adjustable Short Circuit from 1.5 - 8 x Ir - Inbuilt Instantaneous Protection - Provision of Thermal Memory : ON/OFF - Variable trip class at 7.2 Ir & 6 Ir - Front LED indication of Over Load (Ready, Over load pre-alarm & Overload) - Manual, Rotary or Motorised versions available @ - Wide Range of snap fit Internal and External Accessories
lt-dn3-400n-3p-400a
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2039743
Manufacturer Part Number:
CM94003OOR1OG
EAN:
3606481080318
Brand/Manufacturer
L&T ELECTRICAL & AUTOMATION
Unit of Measure:
PCS

Specification

Number of poles:
3
Rated permanent current Iu:
400 A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz:
50 kA
Type of electrical connection of main circuit:
Screw connection