• (0)

TESYS DECA CIRCUIT BREAKER MAGNETIC 40A EVERLINK

GV3L40
2052138

Sign in to view price

TeSys GV motor circuit breaker, 3 poles (3P), 40A/690V, for 3-phase motor applications 18.5kW@400V. It provides a magnetic protection with a tripping level at 14xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary handle guaranteed for 50 000 cycles AC-3. To complete motor protection, use it in association with a thermal overload relay LRD340 (to be ordered separately). Multi standards certified (IEC, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
schneider-gv3l40_PEP1
schneider-gv3l40_Datasheet1
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2052138
Manufacturer Part Number:
GV3L40
EAN:
3389119405447
Brand/Manufacturer
SCHNEIDER ELECTRIC
Unit of Measure:
PCS

Specification

Adjustment range undelayed short-circuit release:
40...40 A
Degree of protection (IP):
IP20
Depth:
136 mm
Device construction:
Complete device in housing
Height:
132 mm
Number of poles:
3
Overload release current setting:
30...30 A
Phase failure sensitive:
yes
Rated operating voltage:
690...690 V
Rated operation power at AC-3, 230 V:
18.5 kW
Rated operation power at AC-3, 400 V:
18.5 kW
Rated permanent current Iu:
40 A
Rated short-circuit breaking capacity Icu at 400 V, AC:
50 kA
Switch off technique:
Magnetic
Type of control element:
Turn button
Type of electrical connection of main circuit:
Screw connection
Width:
55 mm
With integrated auxiliary switch:
no
With integrated under voltage release:
no