• (0)

ACTI9 IPRD8 MODULAR SURGE ARRESTER 1P+N 8KA 350V (MULTIPLY BY 6 PCS)

A9L08500
2158629

Sign in to view price

This Acti9 iPRD8 surge arrester protects 1P+N installations. It allows quick replacement of damaged cartridges. The Imax maximum discharge current is 8kA .The In nominal discharge current is 2.5kA. The iPRD8r ensures secondary protection of loads to be protected and is placed in cascade with the incoming surge arresters. This surge arrester is required when the loads to be protected are at a distance of more than 10 m from the incoming surge arrester. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Uc maximum continuous operating voltage in diiferential mode (between phase and neutral) is 350VAC. The Up Voltage protection level in common mode is 1.4kV between neutral and earth in type 2, and 1.1kV between neutral and earth in type 3. The Up Voltage protection level in differential mode (between phase and neutral) is 1kV in type 2, and 1.1kV in type 3. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 36mm x (H) 85mm x (D) 69mm. The weight is 211g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standards.
SCHNEIDER-A9L08500_PEP1
schneider-a9l08500
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2158629
Manufacturer Part Number:
A9L08500
EAN:
3606480506574
Brand/Manufacturer
SCHNEIDER ELECTRIC
Unit of Measure:
PCS

Specification

Category type 2:
yes
Construction size:
4 modular spacing
Degree of protection (IP):
IP20
Integrated backup fuse:
no
Max. PV-voltage:
0 V
Max. conductor cross section flexible (fine-strand):
35 mm²
Max. conductor cross section solid (solid, stranded):
35 mm²
Max. continuous voltage AC:
350 V
Max. continuous voltage DC:
0 V
Max. discharge surge current (8/20):
8 kA
Mounting method:
DIN rail (top hat rail) 35 mm
Nominal discharge surge current (8/20):
2.5 kA
Nominal voltage AC:
230 V
Nominal voltage DC:
0 V
Signalling at the device:
Optical
System configuration TN-S:
yes
System configuration TT:
yes
Voltage protection level:
1 kV
Voltage protection level L-N:
1.1 kV
Voltage protection level N-PE:
1.4 kV
With remote signalling contact:
no

Reviews

We'd like your opinion! Rate and review this item

There are no reviews from other users.

Recently Viewed