• (0)

5SY4 MCB 2P 6A 10KA

5SY4206-7
2014926

Sign in to view price

All 5SY4 designs have been certified to UL 1077 and CSA 22.2 No. 235-M 89 and therefore can be used as supplementary protectors for applications up to 277 V AC ( 1-pole and 1-pole + N designs) and 480V AC ( 2-Pole, 3-Pole 3-pole + N and 4-pole designs )
siemens-5SY4206-7
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2014926
Manufacturer Part Number:
5SY4206-7
EAN:
4001869181622
Brand/Manufacturer
SIEMENS
Unit of Measure:
PCS

Specification

Additional equipment possible:
yes
Ambient temperature during operating:
-40...70 °C
Built-in depth:
70 mm
Concurrently switching neutral conductor:
no
Connectable conductor cross section multi-wired:
0.75...35 mm²
Connectable conductor cross section solid-core:
0.75...35 mm²
Current limiting class:
3
Degree of protection (IP):
IP20
Explosion-proof:
no
Flush-mounted installation:
no
Frequency:
50...50 Hz
Number of poles (total):
2
Number of protected poles:
2
Over voltage category:
3
Pollution degree:
3
Rated current:
6 A
Rated impulse withstand voltage Uimp:
4 kV
Rated insulation voltage Ui:
440 V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V:
10 kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V:
10 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V:
35 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V:
35 kA
Rated voltage:
400 V
Release characteristic:
C
Voltage type:
AC
Width in number of modular spacings:
2

Reviews

We'd like your opinion! Rate and review this item

There are no reviews from other users.

Recently Viewed