ACTI9 IID RCCB 2P 40A 300MA A-TYPE

A9R25240
2538664

Sign in to view price

This Acti9 iID is a modular and reliable residual current circuit breaker (RCCB). It is a 2P circuit breaker with 40A In rated current, a sensitivity of 300mA with a A type protection class. This product protects against electrical shock by indirect contact and fire hazards. It performs the function of disconnection of electrical circuits in case of earth fault. Its unique Visitrip indicator reduces intervention time by showing the faulty device with a mechanical indicator on front face. This product also has a VisiSafe window with a green strip on the toggle indicating full opening of the poles allowing downstream maintenance This product is compliant with EN/IEC 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 1500A. The (Inc/IΔc) conditional rated short circuit current is 10kA. The mechanical endurance is going up to 20000 cycles and electrical endurance going up to 15000 cycles. The Ue operational voltage is 220VAC to 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 91mm x (D) 73.5mm. The weight is 0.21kg. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -25°C to 60°C. The storage temperature is from -40°C to 85°C.
schneider-a9r25240_Datasheet1
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2538664
Manufacturer Part Number:
A9R25240
EAN:
3606480374517
Brand/Manufacturer
SCHNEIDER ELECTRIC
Unit of Measure:
PCS

Specification

Additional equipment possible:
yes
Ambient temperature during operating:
-25...60 °C
Built-in depth:
73.5 mm
Connectable conductor cross section multi-wired:
1...25 mm²
Connectable conductor cross section solid-core:
1...35 mm²
Degree of protection (IP):
IP20
Explosion-proof:
no
Frequency:
50/60 Hz
Leakage current type:
A
Mounting method:
DIN rail
Number of poles:
2
Pollution degree:
3
Rated current:
40 A
Rated fault current:
0.3 A
Rated impulse withstand voltage Uimp:
6 kV
Rated insulation voltage Ui:
500 V
Rated voltage:
240 V
Selective protection:
yes
Short-circuit breaking capacity (Icw):
10 kA
Short-time delayed tripping:
yes
Surge current capacity:
0.25 kA
Voltage type:
AC
Width in number of modular spacings:
2
With interlocking device:
no